Configuration and Settings – 3
3–1
3
Configuration and Settings
3.1
Relay Configuration .................................................................... 3–1
3.2
Setpoints and Time Settings ..................................................... 3–8
Chapter Three is designed for the person or group
responsible for the configuration of the M-3410A
Intertie/Generator Protection Relay. This chapter
describes the configuration process for the unit
(choosing active functions), output contact
assignment and input blocking designation. It also
illustrates the definition of system quantities,
equipment characteristics required by the protective
relay and describes the individual function settings.
Settings may be entered utilizing M-3810A IPScom
®
for Windows™ or M-3811A IPScom for Palm OS
®
Communications Software (see Chapter 4,
Operation and Interface
).
3.1
Relay Configuration
Functions
Configuration of the relay consists of enabling the
functions for use in a particular application,
designating the output contacts each function will
operate, and which control/status inputs will block
the function. The choices include two programmable
output contacts (OUT1 and OUT2) and two
programmable inputs (IN1 and IN2). A self-test
alarm contact is also provided.
Enabling a relay protective function consists of
entering the required settings in the individual
function screens. Disabling a protective function
(whether settings have been entered or not) is
accomplished by deselecting the individual
protective function element numbers. When a
protective function is disabled, screen values are
grayed out.
The control/status inputs and output contact
assignments must be chosen before entering the
settings for the individual functions. Both should be
recorded on the Relay Configuration Table in
Appendix A,
Configuration Record Forms
for
later use.
The relay configuration also includes the setup of
the Oscillographic Recorder and Sequence of Events
Recorder features. The oscillographic recorder
provides the user with comprehensive data recording
of all monitored waveforms, control/status input
and output status, storing up to 120 cycles of
nonvolatile data. The event recorder provides 32
nonvolatile, time stamped events that include
functions operated, functions picked up and control/
status input and output status.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...