–14–
M-3410A Intertie/Generator Protection Relay
Figure 3
Typical One-Line Diagram–Generator Protection
■
■
■
■
■
NOTES:
1.
The 59G protective function is only available when the relay is configured to use line-to-line VTs
and the 25 function is not enabled.
2.
The 25 protective function is only available when the relay is configured to use line-to-line VTs
and the 59G function is not enabled.
3.
The 32 protective function in single phase detection mode is only available when the relay is
configured to use line-to-ground VT.
*
VTs are not necessary if generator
rated voltage is < 480 V ac.
Utility System
52
Gen
32
40
81
59
47
27
M-3410A Generator Protection
CT
*
46
51V
25
*
51N
60FL
Power
F
R
59G
R
M-3410A
Communications
User Interface with PC
Waveform Capture
(COMTRADE)
Sequence of Events
Logging
Metering
LED Targets
Programmable I/O
OR