M-3410A Instruction Book
3–2
Setup Relay
Nominal Frequency:
60 Hz
50 Hz
C.T. Secondary Rating:
5A
1A
Nominal Voltage: 120
Nominal Current: 5
50 V
0.50 A
500 V
6.00 A
Delta-Y Transform
Enable
Disable
Normal
Latching
Normal
Latching
Output Contact
Mode
1
2
1
2
Open
Close
Open
Close
Input Active State:
VT Configuration:
Line to Ground
Line to Line Line-Ground to Line-Line
User Logo:
Save
Cancel
OK LED Flash:
Enable
Disable
Relay Seal-In Time:
OUT1: 5
OUT2: 5
8160
Cycles
2
Cycles
V.T. Phase Ratio: 1
C.T. Phase Ratio: 1
V.T.
Sync
/V
g
Ratio: 1
:1
:1
:1
1.0
1
1.0
6550.0
65500
6550.0
59/27 Mag. Select:
Phase Rotation:
RMS
ABC
DFT
ACB
Output Relay:
Deenergize to Actuate (Failsafe):
Energize to Actuate:
1
2
Figure 3-1
M-3810A IPScom for Windows Setup Relay Dialog Box
Path:
Relay menu / Setup submenu / Setup Relay command
COMMAND BUTTONS
Save
When connected to a protection system, sends the currently displayed information to the unit.
When working offline (not connected to a relay) but modifying a file, saves the currently displayed
information.
Cancel
Returns you to the IPScom main window; any changes to the displayed information are lost.
■
■
■
■
■
NOTES:
The “active” or asserted states for the individual status inputs are:
1.
Selecting Close causes the “active” or “operated” condition to be initiated by the external contact
closing.
2.
Selecting Open causes the “active” or “operated” condition to be initiated by the external contact
opening.
Relay Setup
The relay setup consists of defining all pertinent
information regarding certain relay actions and
system quantities. The M-3810A IPScom
®
for
Windows™ Setup Relay screen, Figure 3-1, below,
is accessed through the
Relay/Setup, Setup Relay
menu. The M-3811A IPScom for Palm OS
®
Configuration Screens, Figures 3-2, 3-3 and 3-4 are
accessed through the
M-3811A/Setup/
Configuration Menu.
Regardless of the functions
enabled or disabled, all information shown is
required. Several functions require the proper setting
of these values for correct operation. The Nominal
Voltage and Nominal Current settings are needed
for proper normalization of per unit quantities. CT
and VT ratios are used only in monitoring and
displaying system primary quantities.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...