5–13
Testing – 5
32 Directional Power, 3-Phase (#1 or #2) L-L/L-G/L-L
VOLTAGE INPUTS
:
Configuration V1
CURRENT INPUTS
:
Configuration C1
TEST SETTINGS
:
Pickup
P
PU
(–3.00 to +3.00)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
OUT
(1 or 2)
Function 32 (#1 or #2)
Disable
Functions 40, 79
Disable
Q
Q
Q
Q
Q
NOTE
: It would be efficient to disable the function with the lower pickup setting first and test the higher
setting operation. Since the lower setting operation can be tested without disabling the higher
setting, the 32 functions will be enabled when the tests are complete.
1.
Disable functions as shown. See Section 3.2, Setpoints and Time Settings, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 and C1 designated above. See Section 5.1, Equipment/Test
Setup for configurations.
4.
The power in PU can be calculated as follows:
P in PU =
X
X
cos
θ
V
V
nom
I
I
nom
Where V is line-to-ground (L-G) or line-line (L-L) applied voltage as appropriate,
I
is the line current,
and
θ
is the angle between V
A
(L-G) and
I
A.
5.
The level of current at which operation is to be expected for an individual power setting is as
follows: Multiply the PU pickup value (
P
above) by the
Nominal Current
(see Table A-3, System
Setup Record Form).
6.
Set the three phase voltages to the
Nominal Voltage
(see Table A-3, System Setup Record Form).
7.
Pickup Test – Over Power
: Press and hold the
TARGET/OUTPUT RESET
pushbutton and
slowly increase the three phase currents (
for negative or reverse power flow direction, the phase
angle of the phase currents are set at 180 degrees from the respective phase voltages). Increase
the currents until the
DIRECTIONAL PWR 32
LED light illuminates or the pickup indicator
operates on the Function Status screen. The level of operation will be equal to that calculated in
step 5,
&
0.02 PU or
&
2%.
8.
Pickup Test – Under Power
: Press and hold the
TARGET/OUTPUT RESET
pushbutton.
For
negative or reverse power flow direction, the phase angle of the phase currents are set at 180
degrees from the respective phase voltages. Start with a current calculated in Step 5,
&
10%,
then slowly decrease the current until the
DIRECTIONAL PWR 32
LED light illuminates or the
pickup indicator operates on the Function Status screen.
9.
Release the
TARGET/OUTPUT RESET
pushbutton and decrease the currents. Press
TARGET/
OUTPUT RESET
pushbutton to remove targets.
10.
Time Test
: With output contacts
(Z)
connected to stop the timer, apply approximately 110% of
the pickup current and start timing. The contacts will close after
D
cycles within
&
2 cycles.
11.
If testing is complete, enable any functions disabled for this test. If other tests are to be completed,
check the proper functions to disable for the next test and proceed from this configuration.
Q
NOTE
: The above test assumes line-to-ground VT configuration. The test can also be conducted for line-
to-line configuration with 30° phase shift in voltage signals. When L-G to L-L configuration is used,
V in step 4 should be replaced with
S
3 V.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...