M-3410A Instruction Book
5–14
32 Directional Power (#1 or #2) Line-Ground
VOLTAGE INPUTS
:
Configuration V1
CURRENT INPUTS
:
Configuration C1
TEST SETTINGS
:
Pickup
P
PU
(–3.00 to +3.00)
Time Delay
D
Cycles
(1 to 8160)
Programmed Outputs
Z
OUT
(1 or 2)
Function 32 (#1 or #2)
Disable
Function 60FL
Disable
Functions 40, 79
Disable
Q
Q
Q
Q
Q
NOTE
: It would be efficient to disable the function with the lower pickup setting first and test the higher
setting operation. Since the lower setting operation can be tested without disabling the higher
setting, the 32 functions will be enabled when the tests are complete.
1.
Disable functions as shown. See Section 3.2, Setpoints and Time Settings, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 and C1 designated above. See Section 5.1, Equipment/Test
Setup for configurations.
4.
The level of current at which operation is to be expected for an individual power setting is as
follows: Multiply the PU pickup value (
P
above) by the
Nominal Current
(see Table A-3, System
Setup Record Form).
5.
Three-Phase Detect Pickup Test
:
a.
Enable Three-Phase Detection.
b.
Set the three phase voltages to the
Nominal Voltage
(see Table A-3, System Setup Record
Form).
Q
NOTE
: For negative or reverse power flow direction, the phase angle of these currents are set at 180
degrees from their respective phase voltages.
c.
Hold the
TARGET RESET
button in and slowly increase the three-phase current until the
DIRECTIONAL PWR 32
LED light illuminates, or the pickup indicator operates on the
Function Status
screen. The level at which operation occurs will be equal to that calculated
in Step 4,
&
0.02 PU or
&
2%.
6.
Single-Phase Pickup Test
: Disable Three-Phase Detection. Repeat Step #5, using only one
voltage and one current of the same phase.
7.
Release the
TARGET RESET
pushbutton and decrease the currents. The
OUTPUT
LEDs will
extinguish. Press
TARGET RESET
pushbutton to remove targets.
8.
Time Test
:
a.
Connect the output contacts
(Z)
to the timer.
b.
Apply approximately 110% of the pickup current and start timing. The contacts will close after
D
cycles 16 cycles,
&
1%.
9.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...