5–27
Testing – 5
79
Reconnect Time Delay
VOLTAGE INPUTS
:
Configuration V1
CURRENT INPUTS
:
None
TEST SETTINGS
:
Time Delay
D
Cycles
(2 to 65,500)
Reconnect Initiate
R
(1or 2)
Programmed Outputs
Z
OUT
(1 or 2)
1.
Disable functions shown. See Section 3.2, Setpoints and Time Settings, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 designated above. See Section 5.1 Equipment/Test Setup for
configuration.
4.
Adjust the three-phase voltage source to Nominal Voltage (see Table A-3, System Setup Record
Form).
5.
Setup
: Remove the A phase voltage input to cause Function 27 to trip Output
R
(Output
R
will trip
after Function 27 times out).
6.
Time Test
: With output contacts connected to the timer, reapply the A phase voltage input and
start timing. The operation time will be
D
cycles within
&
2 cycles.
7.
Press
TARGET/OUTPUT RESET
pushbutton to remove targets.
8.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this
configuration.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...