M-3410A Instruction Book
3–18
Save
Cancel
(27G) Ground Undervoltage
X
#1
Outputs
Blocking Inputs
2
1
2
1
FL
Pickup:
Delay:
4%
1 Cycle
100%
8160 Cycles
Figure 3-22
M-3810A IPScom
®
for Windows™ (27G) Ground Undervoltage Setup Dialog
Screen
Save
Cancel
(59G) Ground Overvoltage
X
#1
Outputs
Blocking Inputs
2
1
2
1
FL
Pickup:
Delay:
4%
1 Cycle
150%
8160 Cycles
Figure 3-23
M-3810A IPScom for Windows (59G) Ground Overvoltage Setup Dialog Screen
Path
: Relay/Setup/Setpoints/27G Ground Unvdervoltage or 59G Ground Overvoltage
COMMAND BUTTONS
Save
Saves all entered information to the control.
Cancel
Returns you to the previous window; any changes to displayed information are lost.
■
NOTE
: Pickup ranges (%) are of Nominal Voltage.