General operating information regarding the operator level and technician level
While the door is stationary, it is possible to switch from the status level to the parameterisation level for specific door settings. In
parameterisation mode DIP switch PAR=ON, the dot in the first segment on the left flashes.
After 30 minutes without an operating command via the DDT, parameterisation mode is exited once more for safety reasons. After
this time elapses (DIP switch PAR=ON), it is necessary to shift the DIP switch to OFF and back to ON or to reset the voltage in order
to access the password-protected technician level once again.
A parameter is saved by pressing and holding the DDT. The parameter can be considered
saved when the display no longer flashes while the button is being pressed down. The cur-
rent saved value is displayed if the button is briefly pressed. Return to the status level from
the parameterisation level by pressing and holding the rotary-push button (DDT).
Operator level
In this level, running times can be changed and fault messages, clock counters and maintenance counters can be displayed.
1. DIP switch PAR=OFF
2. Press the
DDT and the
button at the same time for 5 seconds.
P.
Description
000
Clock counter
005
Maintenance counter
010
Setting stay-open time 1 (door position at OPEN limit position)
011
Setting stay-open time 2 (door position partially open)
014
Switch-off delay for outdoor light
920
Introduction to the error history
925
Software version
Technician level
Here, various inputs, outputs, functions or times can be reparameterised (see chapter Technician’s parameter overview [
35]).
1. Turn off the power to the control unit.
2. Set the DIP switch PAR to ON.
3. Switch on the power again.
4. Briefly press the DDT(T).
5. Now enter the password in parameter
P.999
.
Changing parameters
1. You get to the desired parameter by pressing the
DDT (R,RR,L,LL).
2. You reach the parameter, and can change it with (R,L,RR,LL) by pressing the
DDT (T) briefly.
3. To save the new value, press the
DDT (TT) until the display no longer flashes.
4. Now briefly press the
DDT (T), and P.xxx will be displayed once more.
5. Any further parameters can be changed by repeating points 1 to 4.
Leave the operator level
Leave the parameterisation mode after the settings have been made.
To do so, press the
DDT (TT) for at least 3 seconds, until the decimal point has flashed twice.
Leave the technician level
Leave the parameterisation mode after the settings have been made.
1. Press the
DDT (TT) for at least 3 seconds, until the decimal point has flashed twice.
2. Turn off the power to the control unit.
3. Set the DIP switch PAR to OFF.
4. Switch the control unit back on.