Technician’s parameter overview
In the following table, all parameters which can be set by the technician are displayed. The values shown for "Setting range" and
"Ex works" pertain to the parameter
P.991:0
(mechanical limit switching)
and may differ from other profiles.
P.
[Unit] Setting
range
Description
Ex works
000
[Cycles]
Door cycle counter
The content of this parameter shows the number of travel cycles counted up to
that moment, and is increased when the OPEN / partial opening limit position is
reached.
0
005
[Cycles]
Maintenance counter
The content of this parameter shows the number of door cycles still to be travelled
until maintenance is due.
0
010
[s]
0..600
Stay-open time 1
The door is kept open in the limit position for the set time, and then closes auto-
matically.
5
011
[s]
0..600
Stay-open time 2
The door is kept open in the limit position for the set time, and then closes auto-
matically.
10
012
0..1
Automatic reclosing (AWZ)
Determines whether the door is closed automatically after the stay-open time has
elapsed and, where applicable, after the advance warning. If the function input
automatic reclosing is in place, this has a higher priority.
0: no AWZ
1: AWZ active
0
014
[s]
0..600
Switch-off delay for outdoor light
The value sets the duration of the switch-off delay for the "Outdoor light" output
function.
120
01A
[s]
0..600
Clearance time for switching green
Clearance time for switching between green inside and green outside. This time is
for allowing the vehicle to pass through the door before it switches to green on the
other side. During this time, both sides flash.
This parameter can only be set if
P.892 is 1.
5
01B
[s]
0..600
Clearance time for switching red
This value sets the duration for clearing the door area in two-way traffic. During the
clearance time, both stop lights flash red.
This parameter can only be set if
P.892 is 1.
20
020
[s]
0..600
Advance warning time prior to opening
The opening of the door is delayed by the amount of time specified in this para-
meter after an OPEN drive command has been input.
0
025
[s]
0..600
Advance warning time prior to closing
The closing of the door is delayed by the amount of time specified in this para-
meter after a CLOSE drive command has been input or after the stay-open time
has elapsed.
0
130
0..1
Motor rotating field
0: Clockwise rotating field
1: Anticlockwise rotating field
0
35