Door profiles
Through the selection of a door profile in the parameter
P.991
, the functions of the inputs and outputs and parameters are preset
to suit a certain type of door. The values specified in the door profiles may therefore differ from the factory default settings of the
door profile 0 (
P.991: 0)
in the overview of parameters, in the description and on the connection and layout plan. The applicable
connecting diagrams and parameters must be observed. Application-specific profiles can be selected with
P.992
.
P.991:0 mechanical limit switching (Becker-Antriebe GmbH)
P.991:1 mechanical limit switching (Becker-Antriebe GmbH)
P.991:2 absolute value encoder (Becker-Antriebe GmbH)
P.992:1 two-way traffic control with M1 expansion board
P.992:2 two-way traffic control with M2 expansion board
P.991:0 mechanical limit switching (Becker-Antriebe GmbH)
Parameter
Input
Function
Terminals
P.4E0
SE 1
Optoelectronic safety edge or electric safety edge
(specified at the initial operation stage)
P.4F0: 3.00
SE 2
Wicket door resistor 8k2 ohm
P.510: 10.00
FE 1
Slack rope NC
P.520: 22.00
FE 2
Light barrier 1
P.530: 13.00
FE 3
Drive command STOP
P.540: 12.00
FE 4
Drive command CLOSE
P.550: 11.02
FE 5
Drive command OPEN
P.560: 8.00
FE 6
Pre-limit switch (VES)
P.570*: 6.00
FE 7
OPEN limit position
P.580*: 7.00
FE 8
CLOSE limit position
*
)
The function inputs FE7 and FE8 cannot be changed if mechanical limit switches are used.
P.991:1 mechanical limit switching (Becker-Antriebe GmbH)
Parameter
Input
Function
Terminals
P.4E0
SE 1
Optoelectronic safety edge or electric safety edge
(specified at the initial operation stage)
P.4F0: 3.00
SE 2
Wicket door resistor 8k2 ohm
P.510: 10.00
FE 1
Slack rope NC
P.520: 22.00
FE 2
Light barrier 1
P.530: 17.01
FE 3
Selection switch automatic reclosing
P.540: 11.02
FE 4
Drive command OPEN
P.550: 14.02
FE 5
Drive command sequence OPEN / STOP / CLOSE
P.560: 8.00
FE 6
Pre-limit switch (VES)
P.570*: 6.00
FE 7
OPEN limit position
P.580*: 7.00
FE 8
CLOSE limit position
*
)
The function inputs FE7 and FE8 cannot be changed if mechanical limit switches are used.
32