![Baxi LUNA HT 1.280 Installation, Operation And Maintenance Manual Download Page 97](http://html1.mh-extra.com/html/baxi/luna-ht-1-280/luna-ht-1-280_installation-operation-and-maintenance-manual_2711826097.webp)
Evaporation heat carrier
(3860)
Pump protecting function, to prevent overheating of the collector pump in case of
evaporating danger of the heat carrying medium due to high collector tempera-
ture.
Antifreeze
(3880)
Information of the antifreeze used.
Antifreeze concentration
(3881)
Input of antifreeze concentration for usage measurement of solar energy.
Pump capacity
(3884)
Input of the flow of the installed pump for calculation of the brought in volume
for usage measurement.
Pulse valency
(3887)
Defines the flow per pulse for the H4 inlet. The H4 inlet must be configured to
pulse count for this.
Solid fuel boiler
Locks other heat sources (4102)
Locks other heat sources
(4102)
If the solid fuel boilers are activated, other heat generators, e.g. oil./gas boilers,
are blocked, as soon as an increase in the boiler temperature is discovered that
points to the exceeding of the comparative temperature (prog. no. 4133).
Setpoint min (4110)
Setpoint min
(4110)
The boiler pump is only put into operation if the boiler temperature has reached
the minimum setpoint set here in addition to the necessary temperature diffe-
rence.
Programming
358 436 08.10
97
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...