Boiler
Setpoint min
(2210)
Setpoint max
(2212)
As a protection function the boiler temperature setpoint can be limited below by
the minimum setpoint (prog.no. 2210) and above by the maximum setpoint
(prog.no. 2212).
Setpoint manual control
(2214)
Temperature, to which the boiler will be contolled in manual control mode (also
see prog. no. 7140).
Burner running time min
(2241)
Here the time span after start up of the burner is set in which the switch off diffe-
rence is increased by 50 %. However, this setting does
not
guarantee that the bur-
ner always remains in operation for the set time span.
Burner off time min
(2243)
The boiler minimum pause time only takes effect between heating requirements
coming following in sequence. The boiler minimum pause time blocks the boiler
for a set time.
SD burner off time
(2245)
When exceeding this switching difference, the
burner pausing time mini-
mum
(prog.-no. 2243) will be interrupted. The boiler starts despite pausing time.
Pump after-run time
(2250)
Pump after-run time after
DHW mode
(2253)
The delay times of the pumps are controlled according to heating mode or drin-
king water mode.
Boiler pump at heat generati-
on lock
(2301)
Stop of boiler pump in case of activated heat generation lock.
-
Off
: Switching off not activated
-
On
: Switching off activated
Impact heat generation lock
(2305)
With these parameter it can be set whether the heat generation lock should be
effective only for heating requests or also for DHW requests.
-
Heating mode only
: Only the heating request is locked. DHW requests will con-
tinue to be operated.
-
Heating and DHW mode
: All heating and DHW requests will be locked.
Temp differential max
(2316)
The limit of the boiler stroke is only possible if a valid value of the boiler return
temperature is available.
Caution!
The limit of the boiler stroke is only performed if a modulating heat cir-
cuit pump is configured, i.e. if Prog. no. 6085 (PWM-output P1) is assigned to a
heating circuit pump.
Temp differential nominal
(2317)
The expansion between boiler flow temperature and boiler return temperature is
called the temperature rise.
For operation with a modulating pump, the temperature rise is limited with this
parameter.
Programming
90
358 436 08.10
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...