![Baxi LUNA HT 1.280 Installation, Operation And Maintenance Manual Download Page 61](http://html1.mh-extra.com/html/baxi/luna-ht-1-280/luna-ht-1-280_installation-operation-and-maintenance-manual_2711826061.webp)
Function
Prog.
no.
Level
1)
Standard value
Charging temp max
4750
E
80°C
Recooling temp
4755
E
60°C
Recooling DHW/HCs
Off | On
4756
E
Off
Recooling collector
Off | Summer | Always
4757
E
Off
With solar integration
No | Yes
4783
E
Yes
Temp diff on return div
4790
E
8°C
Temp diff off return div
4791
E
4°C
Compar temp return div
With B4 | With B41 | With B42
4795
E
With B4
Optg action return diversion
Temp decrease | Temp increase
4796
E
Temp increase
Full charging
Off | Heating mode | Always
4810
E
Off
Full charging temp min
4811
E
8°C
Full charging sensor
With B4 | with B42/41
4813
E
With B42/41
DHW storage tank
Parameter depends on hydraulic system!
Charge push forward time
5011
E
01:00 min
Flow setpoint boost
5020
E
18°C
Transfer boost
5021
E
10°C
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st time
day | Full charg 1st time legio
5022
E
Full charging
Switching diff
5024
E
4°C
Charging time limitation
5030
E
120 min
Discharging protection
Off | Always | Automatically
5040
E
Automatic
Charging temp max
5050
E
65°C
Recooling temp
5055
E
80°C
Recooling collector
Off | Summer | Always
5057
E
Off
El imm heater optg mode
Substitute | Summer | Always
5060
E
Substitute
El immersion heater release
24h/day | DHW release | Time program 4/DHW
5061
E
DHW release
El immersion heater control
External thermostat | DHW sensor
5062
E
DHW sensor
Automatic push
Off | On
5070
E
ON
Excess heat draw
Off | On
5085
E
ON
Programming
358 436 08.10
61
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...