![Baxi LUNA HT 1.280 Installation, Operation And Maintenance Manual Download Page 129](http://html1.mh-extra.com/html/baxi/luna-ht-1-280/luna-ht-1-280_installation-operation-and-maintenance-manual_2711826129.webp)
9.4 Check and replacing Ignition
electrode
Note: To avoid an influence of the ionisation current by the ignition, the ignition
electrode must only immerse into the edge of the flame.
Change ignition electrodes
Danger of electric shock!
Before performing service work, power to the boiler must
be shut off and it must be secured from accidentally being switched back on!
Fig. 34: Remove ignition electrode block
2
1
1. Loosen ignition cable
2. Remove nuts and pull out the ignition electrode block (1) with the seal (2)
3. Insert the new ignition electrode block with seal and fasten with nuts
Note: Installation position and electrode clearance has to be maintained according
to
Fig. 36
.
4. Reconnect the ignition cable
Maintenance
358 436 08.10
129
Power HT 1.230 - 1.280 - 1.320
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...