Duration of the quick setback for setback by
4
°C in h:
Outside temperature composite:
Building time constant (configuration, programme number 6110)
0 hrs
2 hrs
5 hrs
10 hrs
15 hrs
20 hrs
50 hrs
15°C
0
9,7
24,1
10°C
0
3,1
7,7
15,3
23
5°C
0
1,9
4,7
9,3
14
18,6
0°C
0
1,3
3,3
6,7
10
13,4
-5°C
0
1
2,6
5,2
7,8
10,5
26,2
-10°C
0
0,9
2,1
4,3
6,4
8,6
21,5
-15°C
0
0,7
1,8
3,6
5,5
7,3
18,2
-20°C
0
0,6
1,6
3,2
4,7
6,3
15,8
Optimum start control max
(790, 1090, 1390)
Optimum stop control max
(791, 1091, 1391)
The optimization of the on/off switching time is a function of time and possible
with or without the room unit. With a room unit the conversion of the operating
level compared to the programmed time point is moved forward so that the buil-
ding dynamics (heat up and cool down time) is considered. In this way the desired
temperature level is reached exactly at the programmed time point. If this is not
the case (too early or too late) a new switching time point is calculated which is
used the next time.
Without room sensor an advance time point is calculated based on the outside
temperature and the building time constant (prog. no. 6110). The optimization
time (advance) is limited here to a maximum value. By setting the optimization
time = 0, the function is switched off.
Fig. 16: Optimum start and stop control
off
on
Xon
Xoff
ZSP
TRw
TRx
Start time set forward
Stop time set forward
Time switching program
Room temperature setpoint
Room temperature actual value
Programming
82
358 436 08.10
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...