Setpoint source heating
(2056)
When using the generator heating, the swimming pool is heated to the setpoint
set here.
Charging priority solar
(2065)
Setting, of whether the swimming pool heating by solar charging has priority or
not.
Swimming pool temp max
(2070)
This parameter sets whether the swimming pool heating by solar charging has
priority or not. If the swimming pool temp reaches the heating limit set here, the
collector pump is switched off. It is again released if the swimming pool temp has
dropped by 1 °C below the maximum heating limit temperature.
With solar integration
(2080)
Setting, of whether the swimming pool heating can be done by solar energy or
not.
Primary contr/system pump
Flow temp setpoint min
(2110)
Flow temp setpoint max
(2111)
With these boundaries a range for the flow setpoint during heating can be defi-
ned.
Fig. 21: Flow temp setpoint limitations
max
current
min
TV
TFc
TFmax
TFmin
0
10
20
30
40
50
60
70
80
90
100
C0004840
TVmax
TVmin
TVw
TVmax Flow temp setpoint max
TVmin Flow temp setpoint min
TVw Current Flow temp setpoint
Syst pump on heat gen lock
(2121)
This parameter can set whether during active heat generation lock the system
pump will also be locked or not.
-
Off
: The system pump will not be locked.
-
On
: During active heat generation lock the system pump will also be locked.
Mixing valve boost
(2130)
For the admixture the boiler flow temperature actual value must be higher as the
requested setpoint of the mixer flow temperature, since these cannot otherwise
be corrected. The controller from the boiler temperature setpoint from the boost
set here and the current flow temperature setpoint.
Actuator running time
(2134)
Setting the actuator running time of the used mixing valve.
Prim contr/system pump
(2150)
-
Before buffer storage tank
: the primary controller/feed pump is arranged with
existing buffer storage tank hydraulically before the buffer storage tank
-
After buffer storage tank
: the primary controller/feed pump is arranged with
existing buffer storage tank hydraulically after the buffer storage tank
Programming
358 436 08.10
89
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...