Boost heating
(770, 1070, 1370)
The boost heating is active if the room set point is switched from protection mo-
de or reduced mode to comfort mode. During the boost heating the the room set
point is increased to the value set here. This causes the actual room temperature
to increase to the new set point within a short period of time. The boost heating
is ended if the room temperature measured with a RGT/RGTF or RGB (accessories)
room unit increases to 0.25 °C below the comfort set point.
Without room sensor or without room influence the boost heating is carried out
based on an internal calculation. Due to the room set point acting as a basis, the
effect of the duration of the boost heating and that of the flow temperature
works differently for each outside temperature.
Fig. 15: Boost heating
TRSPR
TRw
TRx
DTRSA
Room temperature setpoint
Room temperature actual value
Room temperature set point-raised
Quick setback
(780, 1080, 1380)
The quick setback is active if the room setpoint is switched from comfort level to
another operating level (selected between reduced mode or protection mode).
During the quick setback the heating circuit pump is turned off and the mixing
valve is also closed during mixing circuits. During the quick setback no heat requi-
rement is sent to the heat generator.
The quick setback is possible with or without room sensor: with room sensor the
heating circle function is switched off as long as the room temperature has drop-
ped to the reduced setpoint or frost protection setpoint. If the room temperature
has dropped to the reduced setpoint or the frost protection setpoint, the heating
circuit pump is switched on again and the mixing valve is released. Without the
room sensor the quick setback switched the heater off depending on the outside
temperature and the building time constant (prog.no. 6110) as long as the tem-
perature has theoretically dropped to the reduced target value or the frost protec-
tion value.
Duration of the quick setback for setback by
2
°C in h:
(e.g. comfort sepoint = 20°C, reduced setpoint = 18°C)
Outside temperature composite:
Building time constant (configuration, programme number 6110)
0 hrs
2 hrs
5 hrs
10 hrs
15 hrs
20 hrs
50 hrs
15°C
0
3,1
7,7
15,3
23
10°C
0
1,3
3,3
6,7
10
13,4
5°C
0
0,9
2,1
4,3
6,4
8,6
21,5
0°C
0
0,6
1,6
3,2
4,7
6,3
15,8
-5°C
0
0,5
1,3
2,5
3,8
5
12,5
Programming
358 436 08.10
81
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...