9.9 Clean fan
Dismounting the burner
1. Remove burner (see section
Installing and removing burner
)
Fig. 41: Remove fan
1
2
3
4
2. Remove nuts with washers and release the fan (3) with seal (2) from burner co-
ver (1)
3. Remove screws and release venturi pipe, incl. gas valve (5) with seal (4) from
fan
4. Clean fan with compressed air
5. Reassemble burner in the opposite sequence
Note: Use new seals when reassembling the burner.
6. Reinstall burner (see section
Installing and removing burner
)
9.10 Control and regulating
centre LMS
Description of function
Control and monitoring of the burner with control and regulating centre LMS, with
ionisation electrode.
Automatic start according to programme with monitoring of flame forming. The
sequence itself may be varied via parameters.
Maintenance
134
358 436 08.10
Summary of Contents for LUNA HT 1.280
Page 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Page 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Page 10: ...Technical Data 10 358 436 08 10...
Page 12: ...Technical Data 12 358 436 08 10...
Page 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Page 21: ...Before installation 358 436 08 10 21...
Page 23: ...Wiring plan Before installation 358 436 08 10 23...
Page 25: ...Wiring plan Before installation 358 436 08 10 25...
Page 27: ...Wiring plan Before installation 358 436 08 10 27...
Page 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Page 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Page 31: ...4 9 Legend Before installation 358 436 08 10 31...
Page 142: ...Space for notes 142 358 436 08 10...
Page 143: ...Space for notes 358 436 08 10 143...