Installation
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
191
7
7.10.3 Electrical connection power unit
1)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm
2
, you may also use stronger
cables than 95 mm
2
2)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm
2
, you may also use stron-
ger cables than 185 mm
2
. Also see
3)
One cable of the mentioned cross section is sufficient for the operation.
4)
Power system
1U1, 1V1, 1W1, PE
Max. cross-section
of connection
Connection
technology
Torque
Load capacity
BM441X
2.5 mm
2
Plug-in contact
-
see
not v
alid for
po
we
r mo
dule
s
BM442X
4.0 mm
2
Screw terminal
min. 0.5 Nm
max. 0.6 Nm
BM443X
Generation 1
4)
10 mm
2
Screw terminal
min. 1.2 Nm
max. 1.5 Nm
BM443X
Generation 2
4)
BM463X
25 mm
2
Screw terminal
min. 2 Nm
max. 2.3 Nm
BM444X
BM464X
50 mm
2
Screw terminal
min. 6 Nm
max. 8 Nm
BM445X
BM465X
BM475X
2 x 95 mm
2 1)3)
Cable lug
for M8
min. 10 Nm
max. 13 Nm
BM446X
BM466X
BM476X
2 x 185 mm
2 2)3)
Cable lug
for M10
min. 12 Nm
max. 25 Nm
BM447X
BM477X
2 x 185 mm
2 2)
4 x 95 mm
2 1)
Cable lug
for M10
min. 12 Nm
max. 25 Nm