Design and Operation
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
131
4
4.6
UL notes
The notes below must be observed at a
c
c
- conformity drive.
In case you consider UL 508 C observe the notes below also:
m
>
Parameter manual b maXX 4400, 4600, 4700
<
n
Adjustment for motor overload monitoring (I
2
t)
m
Requirements to the connecting cables
n
Use 60 °C/75 °C copper wire only for all devices
n
Use Class 1 wire only.
m
Electrical connection power unit
n
Note tightening torque for connection terminals.
m
Only for water-cooled devices:
n
In order to avoid internal condensation: The temperature of cooling water supply
must be higher or at least equal to the internal temperature of the device.
n
Maximum cooling water temperature 60°C
n
Maximum water pressure 3 bar / 300 kPa in the cooling circuit.
m
Required environmental conditions
n
Use the device only in a pollution degree 2 environment
n
Observe the maximum environmental temperature and the derating
m
Requirements to the energy supply / supply system
n
Observe the short circuit current capability.
The device is rated for a maximum Short Circuit Current Rating (SCCR) of 65 kA,
480 V AC.
n
24 V supply must not reach more than 30 V DC. Additional fuse protection with max.
4 A fuse.
m
n
Converters may be used with listed fuses or listed circuit breakers DIVQ as overcur-
rent protection.
m
Requirements for the motor temperature sensors
n
Observe the connecting data of the motor temperature sensor.
cUL notes
Additional only for Canada:
NOTE
Overvoltage Protection Device have to be installed in front of the input circuit of the
device to limit the maximum overvoltage peak to 2.5 kV.