Installation procedure
h
Lay all cables EMC-compatible.
h
(Observe the torques!)
The following steps must be carried out at installation:
1
Connect the motor through terminals 1U2, 1V2, 1W2 and PE.
Ensure the proper phases when connecting (rotational direction).
Observe the permitted torques!
2
Connect fuses (S1) -
not necessary for power modules
(in case you consider UL 508 C: use the UL-listed semiconductor- or total-range-
fuses in chapter
3
Connect mains filter (L2) -
not necessary for power modules
.
4
Connect the power choke (L1) at the mains filter output
(
not necessary for BM441X, BM442X (except BM4426) and for power modules
).
5
Connect the device via the power supply terminals 1U1, 1V1 and 1W1 to the power
choke output -
not necessary for power modules
.
6
Connect the protective conductor to the terminal PE (a fixed ground conductor con-
nection is mandatorily specified).
7
Connect 24 V power supply:
Terminals X100-1/2, X100-5/6
(if UL 508C is being considered, then limit the current to 4 A).
DANGER!
Risk of fatal injury from electrical current!
Electrically live parts are life-threatening.
Therefore:
m
Make certain that the parts to be mounted (e.g. power supply cables) and the
mounting areas are de-energized for the entire duration of mounting the device.