Fuses
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
Baumüller Nürnberg GmbH
274
11.2
Device protection
Use semiconductor fuses with the tripping characteristic aR (DIN VDE 0636-201 / IEC
60269-2-1 / HD 630.2.1 54). Connect these in series with the cable protection fuses. In
the event of a short circuit, these protect the line-side rectifier unit circuit on the input side
against complete destruction, in order that it is possible to repair the device.
Dimension suitable device protection fuses depending on peak current and the maximum
load integral i
2
t
off
.
1)
Use fuses that fall below the specified cutoff integral (i
2
t
aus
)
in the operating point
.
Device
Maximum load integral
1)
BM44
12
310 A
2
s
BM44
13
310 A
2
s
BM44
14
325 A
2
s
BM44
22
400 A
2
s
BM44
23
450 A
2
s
BM44
24
800 A
2
s
BM44
25
800 A
2
s
BM44
26
800 A
2
s
BM44
3X
(generation 1)
1.500 A
2
s
BM44
3X
(generation 2,
see
BM46
3X
9.500 A
2
s
BM44
4X
BM46
4X
b
16 200 A
2
s
BM44
5X
BM46
5X
BM47
5X
97 000 A
2
s
BM44
6X
BM46
6X
BM47
6X
245 000 A
2
s
BM44
7X
BM47
7X
1 051 000 A
2
s