Cabling
Instruction handbook
b maXX
BM4400, BM4600, BM4700
Document No.: 5.12008.07
Baumüller Nürnberg GmbH
268
11.1
11.1 Cabling
11.1.1 Cables power supply-device
Device
Number of wires x
cross section
1)
Connection to device
3)
Maximum length
2)
BM44
1X
4 x 0.5 to 2.5 mm
2
(AWG 16 - 12)
flexible cable
with/without wire end ferrule
(plug-in terminal)
power supply to mains filter:
user-defined
mains filter to power choke/
device: max. 30 cm
BM44
2X
4 x 0.5 to 4 mm
2
(AWG 24 - 10)
flexible cable with wire end ferrule
(screw terminal)
BM44
32
BM44
33
BM44
34
4 x 0.5 to 10 mm
2
(AWG 20 - 6)
flexible cable with wire end ferrule
(screw terminal)
BM44
35
4)
4 x 16 mm
2
63 A-fuses must be provided
for the cable protection and a
cable with 16 mm
2
cross sec-
tion must be used.
pin-cable-lugs according to DIN
46230
The terminals at the BM4435 are provided for
cross sections up to 10 mm
2
, therefore at the
BM4435 pin-cable-lugs according to DIN
46230 must be used.
BM46
32
4 x 25 mm
2
63 A-fuses must be provided
for the cable protection and a
cable with 25 mm
2
cross sec-
tion must be used.
flexible cable with wire end ferrule
(screw terminal)
BM44
4X
BM46
4X
4 x 16 to 50 mm
2
(AWG 6 -0)
flexible cable with wire end ferrule
(screw terminal)
BM44
5X
BM46
5X
BM47
5X
4 x 25 to ca. 185 mm
2
cable lug max. width: 25 mm
(current bar)
5)
BM44
6X
BM46
6X
BM47
6X
cable lug max. width: 35 mm
(current bar)
6)
BM44
7X
BM47
7X
max. 4 cables with
(4 x 95 mm
2
)
max. 2 cables with
(4 x 185 mm
2
)
cable lug max. width: 25 mm or
35 mm (current bar)
7)
1)
Possible cross section
For UL conform machines/installations you must use UL certified circuit cables.
2)
The length of the cable between mains filter and power supply is not of importance for the compliance to the EMC regulation.
3)
The installing of the cables is user-defined.
4)
NOTE BM4435, BM4635
The BM4435 has an input current of 53 A, the appropriate mains filter (BFN3-1-56-001) has a rated current of 53 A, too.