58
english
5.7
Operating Hours Counter
5.7.1 Description
The operating hours counter can record the operating
hours of a device accurately to the second. There are a
total of three operating hours counters. In addition to an
operating hours counter for the operating hours since the
start of the device, there is a total operating hours counter
and a customer-specific operating hours counter that can
be reset. The storage rate can be set and no operating
hours are stored upon reaching 1,000,000 storage cycles.
The output of the operating hours can serve as a time
control for the service interval as well as for preventative
maintenance. Schedules for regular service can be tied to
the operating hour values. Moreover, a high value of the
total operating hours is indicative of intensive use of a
sensor and possible deterioration of the performance. The
risk of failure can be countered preventatively through
replacement.
5.7.2 Algorithm
While the counter is incremented every second, the
storage rate doubles after each save operation. Starting
with a save operation after 1 minute, then after 2 minutes,
then after 4 minutes, then after 8 minutes, until a maximum
storage rate of every 12 minutes.
5.7.3 Process Data
Object ID
Name
Description
Direction
0x001B (27)
Current Operating Hours
Output of the current operating hours counter
Input
0x001C (28)
Total Operating Hours
Output of the total operating hours counter
Input
0x001D (29)
Custom Operating Hours
Output of a user-defined operating hours counter
Input
Tab. 5-33: Operating hours counter – Process data
5.7.4 ISDU
Name
Index
Subindex
Access
Length
Data Type
Data
Storage
Default
Current Operating
Hours
0x0057 (87)
1
R
4 byte
UINT32
No
0
Total Operating
Hours
0x0057 (87)
2
R
4 byte
UINT32
No
0
Custom Operating
Hours
0x0057 (87)
3
R
4 byte
UINT32
No
0
Operating Hours
Saving Mode
0x0074 (116)
0
R/W
1 byte
ENUM
Yes
0
Tab. 5-34: Operating hours counter – ISDU
The maximum counter value that can be saved is
1,000,000 and, with a switch-on and switch-off
every 12 minutes (with static counter), means a
service life of over 20 years.
If switched on and off more frequently or in the
case of dynamic storage, the maximum storage
time is reduced depending on the application.
5
Secondary Device Functions (continued)
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Summary of Contents for IO-Link BES M12EH1-L01C40B-S04G-L04
Page 2: ...www balluff com...
Page 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Page 96: ...www balluff com...
Page 187: ......