42
english
5.3.4 ISDU
Name
Index
Subindex
Access
Length
Data Type
Data
Storage
Default
Switching
Speed
0x009B (155)
0
R/W
6 byte
Yes
Input
1
R/W
2 bytes
ENUM
No
0
Mode
2
R/W
1 byte
ENUM
No
0
Speed Upper
Limit High
3
R/W
2 bytes
UINT16
No
100
Speed Upper
Limit Low
4
R/W
2 bytes
UINT16
No
85
Speed Lower
Limit High
5
R/W
2 bytes
UINT16
No
65
Speed Lower
Limit Low
6
R/W
2 bytes
UINT16
No
50
Startup Delay
7
R/W
1 byte
UINT8
No
0
Switching
Speed Status
0x009C (156)
0
R
3 byte
No
State
1
R
1 byte
ENUM
No
Value
2
R
2 bytes
UINT16
No
Tab. 5-10: Signal Speed Monitor – ISDU
Speed Monitoring Input
With
Speed Monitoring Input
, the internal binary signal
source can be selected.
Input
contains a list of the internal
binary signals .
Speed Monitoring Mode
With
Speed Monitoring Mode
, the current mode of the
counter function can be selected.
Value
Meaning
Description
0x00 (0) Deactivated
Deactivated
0x01 (1) Speed
Speed monitoring
Tab. 5-11: Speed Monitoring Mode
Speed Upper Limit High
In combination with
Speed Upper Limit Low
, it forms a
threshold value with hysteresis for the
too high
status.
Speed Upper Limit Low
In combination with
Speed Upper Limit High
, it forms a
threshold value with hysteresis for the
too high
status.
Speed Lower Limit High
In combination with
Speed Lower Limit Low
, it forms a
threshold value with hysteresis for the
too low
status.
5
Secondary Device Functions (continued)
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
Summary of Contents for IO-Link BES M12EH1-L01C40B-S04G-L04
Page 2: ...www balluff com...
Page 3: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Konfiguration deutsch...
Page 4: ...www balluff com...
Page 95: ...BES M12EH1 L01C40B S04G L04 BES M18EH1 L01C80B S04G L04 IO Link Configuration english...
Page 96: ...www balluff com...
Page 187: ......