Switching Counter
5.4.1 Description
With the
Switching Counter
, events (e.g.: object
detections) can be counted.
5.4.2 Mathematics/Algorithm
Switching Counter – Static Mode
On every rising edge of the input signal, the counter value
is increased (see Fig. 5-3).
If the counter value is less than the configured counter
limit, the counter state flag
not reached
is set. As soon as
the count value is greater than or equal to the configured
counter limit, the counter state flag
reached
is set. If the
count value is greater than the configured counter limit, the
counter state flag
exceeded
is set.
The count value can be reset at any time by a system
command (count value = zero).
Fig. 5-3: Switching Counter – Static Mode
5
Secondary Device Functions (continued)
BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors