Fan Pump 3 Wire Control Mode
Figure 3-15 Fan Pump, 3 Wire Control Connection Diagram
PRESET SPEED #1
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
ENABLE
FORWARD RUN
REVERSE RUN
STOP
RUN COMMAND
SPEED COMMAND
EXTERNAL TRIP
OPTO INPUT COMMON
Programmable 0–5v Output (Factory Preset: Speed)
J1
ANALOG GND
ANALOG INPUT 1
POT REFERENCE
ANALOG INPUT +2
ANALOG INPUT –2
ANALOG OUT 1
ANALOG OUT 2
OPTO OUT COMMON
OPTO OUT #1
OPTO OUT #2
OPTO OUT #3
OPTO OUT #4
1
2
3
4
5
6
7
Programmable 0–5v Output (Factory Preset: Current)
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
23
24
25
26
27
28
29
+24VDC
OPTO IN POWER
OPTO OUT #1 RETURN
OPTO OUT #2 RETURN
OPTO OUT #3 RETURN
OPTO OUT #4 RETURN
PRESET SPEED #2
Note 3
Notes 1 and 2
Note 5
0-10VDC or
5k
W
Command Pot
Note 1
±
5VDC,
±
10VDC or 4-20mA.
Notes:
1.
Refer to Analog Inputs.
2.
Refer to Figure 3-21 for 4-20mA.
3.
Refer to Analog Outputs.
4.
Refer to Opto Isolated Inputs.
5.
Refer to Opto Isolated Outputs.
6.
Refer to Encoder installation.
7.
Refer to Buffered Encoder Output.
Note 4
Both CLOSED=
Fault Reset
COMMON
A
A
B
B
INDEX
INDEX
+5VDC
COMMON
A
A
B
B
INDEX
INDEX
Not Used
Encoder
Input
Note 6
Buffered
Encoder
Output
Note 7
Refer to
Figure 3-23.
J1-8
OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor.
J1-9
MOMENTARY CLOSED starts motor operation in the Forward direction.
J1-10
MOMENTARY CLOSED starts motor operation in the Reverse direction.
J1-11
When OPEN motor Decels to stop.
J1-12
Run Command. OPEN selects STOP/START and Reset commands from Keypad.
CLOSED selects STOP/START and Reset commands from terminal strip.
J1-13
Speed Command. OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block,
Command Select parameter).
Note: When changing from Keypad to Terminal Strip (J1-12 or J1-13) the motor speed and
direction will remain the same after the change.
J1-14
OPEN selects preset speed #1 regardless of the Speed Command input J1-13.
(FIRESTAT)
J1-15
OPEN selects preset speed #2 regardless of the Speed Command input J1-13.
(FREEZESTAT)
Note: If J1-14 and J1-15 are both Open, Preset Speed #1 is selected.
J1-16
OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed “ON”. When this occurs, the drive is disabled
and an external trip fault is displayed on the keypad display (also logged into the fault
log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
Summary of Contents for 22H series
Page 5: ...Section 1 General Information iv Table of Contents MN722...
Page 105: ...Section 1 General Information 5 22 Troubleshooting MN722...
Page 109: ...Section 1 General Information 6 4 Manual Tuning the Series 22H Control MN722...
Page 137: ...Section 1 General Information A 8 Appendix A MN722...
Page 138: ...Appendix B Appendix B 1 MN722...