PTS PRESSURE TRANSMITTER
CALIBRATION
WBPEEUI110501A0
F - 7
Rezero
The rezero procedure allows you to zero the transmitter without going
through the complete bench calibration procedure.
Adjust the transmitter output using the up and down arrow
keys.
Bench calibration is complete.
Key
Display
Comments
ENTER
ADJUST TO 20 mA
THEN HIT ENTER
ENTER
CONFIG. ID TAG
READY
Key
Display
Comments
Select
REZERO
.
If digitally configured, the
D-TO-A ADJUST
selection will
not appear.
Apply zero value to the transmitter.
Rezero is complete.
CALI-
BRATE
OUTPUT WILL BE
AFFECTED
PROCEED?
NO
→
YES
ENTER
CALIBRATION:
D-TO-A ADJUST
BENCH CALIB.
→
REZERO
ENTER
APPLY PRESSURE
OF
nn.nn UNITS
THEN HIT ENTER
ENTER
CONFIG. ID TAG
READY