BCN PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
B - 2
WBPEEUI110501A0
A configuration can be created off-line, without a connected field device. A
number of configurations can be created and stored in the terminal, and sent
to a field device at a later time with
.
A series of
n
s may appear in the
Display
column of this instruction where
numeric characters can be displayed or entered. The STT03E terminal is
assumed to be in the
READY
state when beginning the following procedures.
Figure B-1. Configuration Flowchart (BCN)
ENTER
DAMPING
CONSTANT
SELECT
OUTPUT
ACTION
IDTAG
ENTER
CHANNEL
NUMBER
ENTER
SECONDARY
UPPERRANGE
SAVE
CONFIGURATION
DIGITAL
ANALOG
SELECT
TRANSMITTER
TYPE
ENTER UPPER
RANGEVALUE
ENTER LOWER
RANGEVALUE
ENTER
SECONDARY
LOWER RANGE
SELECT
OUTPUTTYPE
SELECT
INITIALIZE
MODE
TP30217A
SELECT FAIL
MODE
ENTER
SECONDARY
UNITS
SELECT
ENGINEERING
UNITS
C
O
N
F
I
G
U
R
E
SELECT
MODE
SEND CONFIG
Key
Display
Comments
Select
NEW
to create a new configuration.
To modify an
existing configuration, select
MODIFY.
The screen
sequence is the same, however, the
MODIFY
screens will
appear with the values and cursor positions as originally
configured.
Enter a name for the configuration (also known as ID tag)
using up to 12 ASCII characters. To select a character,
scroll through the list (refer to Table
) using the up and
down arrow keys. Use the right arrow key to move to the
next digit. To change a character, use the left arrow key to
backspace.
Select
DIGITAL
(device in this mode defaults to below 4
mA, independent of input). Use the up and down arrow
keys to select mode.
NOTE:
The
DIGITAL
selection should only be made
when using an IMFBS01 field bus I/O module. Select
ANALOG f
or all other cases.
CONFIG
CONFIGURATION
→
NEW
MODIFY
ERASE
ENTER
STT03 CONFIG
[nnnnnnnnnnnnn]
ENTER
SELECT MODE:
ANALOG
→
DIGITAL