AVS SMART POSITIONER
CALIBRATION
WBPEEUI110501A0
A - 7
Output D-to-A Calibration
The
D-TO-A ADJUST
selection is only present when you are in the
ANA-
LOG
communication mode, specified in the configuration procedure. This
selection allows you to adjust the four to 20 milliampere output of the field
device.
NOTE:
Analog board must be installed for this function.
Key
Display
Comments
Select the desired calibration.
Use the up and down arrow keys to adjust the 4 mA signal.
NOTE:
When increasing or decreasing the mA signal, the
increments of change increase with successive depressions
until the maximum level of change is reached. By chang-
ing direction you will return to the smallest increment of
change. This adjustment technique speeds up the adjust-
ment process without affecting fine adjustment.
Use
the up and
down arrow keys to adjust the 20 mA sig-
nal.
NOTE:
Refer to AVS instruction for details on the cali-
brations.
CALI-
BRATE
OUTPUT WILL BE
AFFECTED
PROCEED?
NO
→
YES
ENTER
→
OUTPUT D/A CAL
INPUT A/D CAL
MAN POS CAL
AUTO POS CAL
ENTER
ADJUST TO 4mA
THEN HIT ENTER
ENTER
ADJUST TO 20 mA
THEN HIT ENTER
ENTER
CONFIG. ID TAG
READY