EQS TEMPERATURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
D - 2
WBPEEUI110501A0
A configuration can be created off-line, without a connected field device. A
number of configurations can be created and stored in the terminal and sent
to a field device at a later time with
.
A series of
n
s may appear in the
Display
column of this instruction where
alphanumeric characters can be displayed or entered. The STT03E terminal
is assumed to be in the
READY
state when beginning the following proce-
dures
.
Figure D-1. Configuration Flowchart (EQS)
NO. OF
WIRES
ENGINEERING
UNITS
SELECT INITIALIZE
MODE
UPPERTEMP
ALARM
NO. OF
ELEMENTS
NO. OF
WIRES
ENTER UPPER
RANGE VALUE
LOWERTEMP
ALARM
IDTAG
OUTPUT TYPE
SELECTFAIL
MODE
SELECTMODE
OUTPUT
ACTION
ENTER
SECONDARY UNITS
ENTER CHANNEL
NUMBER
DIGITAL
ANALOG
T/C
RTD
mV
OHMS
SELECT
TRANSMITTER
TYPE
DAMPING
CONSTANT
ENTER
SECONDARY
LOWER RANGE
SAVE
CONFIGURATION
SELECT
RTDTYPE
NO. OF
ELEMENTS
SELECT
THERMOCOUPLE
TYPE
ENTER LOWER
RANGE VALUE
ENTER
SECONDARY
UPPER RANGE
TP81001A
C
O
N
F
I
G
U
R
E
SEND CONFIG
Key
Display
Comments
Select
NEW
to create a new configuration.
To modify an
existing configuration, select
MODIFY.
The screen
sequence is the same, however, the
MODIFY
screens will
appear with the values and cursor positions as originally
configured.
A 14-character ID tag name is entered within the brackets.
Use the arrow keys to select characters. Use the right
arrow to advance to the next character. When finished
entering a name press
.
CONFIG
CONFIGURATION
→
NEW
MODIFY
ERASE
ENTER
STT03 CONFIG
[nnnnnnnnnnnnn]
ENTER