BCN PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
WBPEEUI110501A0
B - 3
If
ANALOG
is selected,
ENTER CHANNEL #
screen will
not appear. The next screen will be
TRANSMITTER TYPE.
This screen is used to assign an address to the transmitter
for use with the field bus. The address range is 1 through
15.
Choose
BCN.
Move the indicator to the choice with the up and down
arrow keys. Refer to the
Smart Pressure Transmitter Type
BCN
instruction for output types.
For this example
FUNC GEN
is the output type.
NOTE:
The STT03E terminal is capable of displaying 3
output types on the screen. Use the up and down arrow
keys to view the additional output types.
Five input and output points need to be specified as a per-
centage of input. The first and last points on the curve are
assumed to be 0.00% and 100.00%. Use the number keys
to enter a value. Press
. Continue until all 5 pairs
of points have been entered.
Move the indicator to your selection.
Refer to the
Smart Pressure Transmitter Type BCN
instruction for an explanation of terms.
Key
Display
Comments
ENTER
ENTER CHANNEL #:
nn
ENTER
TRANSMITTER TYPE
→
BCN
EQN
ENTER
OUTPUT TYPE
→
LINEAR
SQUARE ROOT
3/2 FLOW MODE
OUTPUT TYPE
3/2 FLOW MODE
5/2 FLOW MODE
→
FUNC GEN
ENTER
POINT 1 INP (%)
nn.nn
POINT 1 OUT (%)
nn.nn
ENTER
POINT 5 INP (%)
nn.nn
POINT 5 OUT (%)
nn.nn
ENTER
OUTPUT ACTION:
→
NORMAL
REVERSE