In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 53
Step
Actions to be taken
Display Indication
Audible Indication
12b
To silence all alarms,
press the red Silence
Alarms button.
All Fire Alarm Devices
(FAD) are deactivated.
Comments:
The red
FIRE
indicator goes steady.
To
manually
resound the alarm zones at this stage, Action Digit 1
(RESOUND) can be pressed.
The alarm zones previously in alarm state are
automatically
resounded to
their alarm state on timeout of the silence resound timer.
When the fire is extinguished and all necessary repair work is implemented
(smoke is exhausted, new glass replaced in the manual call-points, etc.), the
system should be returned to normal operating mode.
The SILENCE ALARMS button has to be pressed before pressing the
RESET button. Otherwise the reset operation will be rejected without having
any effect on system behaviour.
13b
Press the green Reset
button.
All audible indicators
within the operation
zone of the operator
panel are turned off.
Comments:
If there are no points signalling a fire alarm, the system is reset.
The red
FIRE
indicator goes off.
The red
Fire Brig. Signalled
indicator goes off.
If there are points still signalling a fire alarm, refer to step 10 in the procedure
described in chapter 5.2.
SILENCE
Info:
Completed
FIRE ALARMS
Total: 1
1 KITCHEN
19:23
SILENCE
Info:
Completed
FIRE ALARMS
Total: 1
1 KITCHEN
19:23
1: RESOUND
4: SHOW SUPPR. INFO
FIRE ALARMS
19:23
Total: 1
1 KITCHEN
1: RESOUND
4: SHOW SUPPR. INFO
FIRE ALARMS
19:23
Total: 1
1 KITCHEN
RESET
Info : Completed
19:23
RESET
Info : Completed
19:23
IMMEDIATE ACTIONING DELAYED
1 HOUSE
DISABLEMENTS
19:23
Total: 1
Total: 1
IMMEDIATE ACTIONING DELAYED
1 HOUSE
DISABLEMENTS
19:23
Total: 1
Total: 1