In the Event of a Fire Alarm
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 49
Step
Actions to be taken
Display Indication
Audible Indication
The point(s) still in alarm will be
shown on the display.
If no actions are taken
, the
points still signalling alarm will
automatically be
reactivated
after a predefined timeout.
If you want to
disable the
point(s
) - for example, a manual
call-point -still signalling alarm,
go to step 11. The points can
also be reactivated (step 12) at
any time after the disablement
(ALARMDISABLE) has taken
place.
11
To disable all points still
signalling alarm, press
Comments:
The red
Fire Brig. Signalled
indicator goes off.
The yellow
Function Disabled
indicator is lit.
All point(s) still signalling alarm are disabled. To reactivate the point(s), you
have to press Action Digit 3 (REACTIVATE).
12
To reactivate the
point(s), press Action
Digit 3.
The point(s) will again
signal alarm.
The internal buzzer on
the operator panel is
turned on.
Comments:
The yellow
Function Disabled
indicator goes off.
The red
FIRE
indicator starts to blink.
The red
Fire Brig. Signalled
indicator is lit.
13
To reset the system,
repeat step 9 and 10.
(Press the red Silence
Alarms button and the
green Reset button).
Comments:
If there are no points signalling a fire alarm, the system is reset.
The red
FIRE
indicator goes off.
The red
Fire Brig. Signalled
indicator goes off.
The panel enters its idle state.
RESET
19:23
RESET
19:23
POINTS IN ALARM
P6
Press ‘ENTER’ to disable all points.
19:23
POINTS IN ALARM
P6
Press ‘ENTER’ to disable all points.
19:23
ALARM DISABLE
19:23
ALARM DISABLE
19:23
RESET
19:23
RESET
19:23
DISABLED POINTS
Total: 1
1 P6
DISABLEMENT
19:23
Total: 1
3: REACTIVATE
DISABLED POINTS
Total: 1
1 P6
DISABLEMENT
19:23
Total: 1
3: REACTIVATE
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
REACTIVATE
19:23
REACTIVATE
19:23
SILENCE
19:23
SILENCE
19:23
RESET
19:23
RESET
19:23
AUTROSAFE
SelfVerify
AUTROSAFE
SelfVerify