Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 140
14.9 Dual Safety
Dual Safety
Transfer to Primary
Transfer to Secondary
14.9.1 Transfer to Primary / Secondary System
During normal operation, the Primary System is in Active Mode, i.e.
the system controls the detection loops, while the Secondary System
is in Standby Mode.
This command allows you to transfer the control of detection loops
from the Primary System to the Secondary System (Transfer to
Secondary), or vice versa (Transfer to Primary).
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press the Menu button
2
To select SERVICE, press 5.
3
To select DUAL SAFETY, press 7.
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 REPORT
5 UPGRADE
6 REMOTE ACCESS
7 DUAL SAFETY
8 OIL & GAS COMMANDS
MENU
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
DUAL SAFETY
19:23
1 TRANSFER TO PRIMARY
2 TRANSFER TO SECONDARY