Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 130
Step
Actions to be taken
Display Indication
5
To view detailed point information for this
detector, press
Comments:
The point information includes the point’s
tagname followed by the Loop Sequence
Number (LSI), the name of the zone, the loop
and its corresponding loop driver module’s
physical position in the module stack inside the
cabinet (counted from bottom to top above the
BSL-310 board), the Fire Alarm Control Panel’s
name and its address, and finally the exact time
and date when this point was reported as
polluted.
14.6.3 SV Reports to USB
This command copies SV reports to a USB memory stick for.
all detectors in system
all detectors “Not OK” in system
Reports shall include:
UnitName
Date and time of last OK SV test
Date and time of last SV test
SV fault counter
Last test result
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press the Menu button
2
To select SERVICE, press 5.
POINT LOCATION
19:23
4: PRINT
Polluted
1 Heat Detector1
1.0
Zone2
Loop 1
(01)
BS-320
(01)
08:05:03 2007-06-27
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE