Service Commands
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 109
14.3.2.5 Manual Test ON - Other Outputs
This chapter describes how to test other outputs (outputs to
Fire
Protection Equipment)
. The test requires Access Level 3 (password
restricted).
When the test is initiated, a test signal will be sent to the selected Fire
Protection Equipment.
Step
Actions to be taken
Display Indication
1
To enter the Main Menu, press the Menu button
2
To select SERVICE, press 5.
3
To select TEST, press 1.
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 REPORT
5 UPGRADE
6 REMOTE ACCESS
7 DUAL SAFETY
8 OIL & GAS COMMANDS
SERVICE
TEST
1 DETECTION ZONE TEST (EN 54)
2 OUTPUT TEST
19:23
NOTE:
Before this test is performed, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is to
be tested.