![Autronica BS-420 Operator'S Handbook Manual Download Page 12](http://html1.mh-extra.com/html/autronica/bs-420/bs-420_operators-handbook-manual_3023434012.webp)
Panel Overview
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 12
2.3 Repeater Panel BU-BV-420
The Repeater Panel BU-BV-420 serves as both a Fire Brigade Panel
and an Information Panel.
Settings on a dipswitch determines the type of panel. Each panel type
is described in the following chapters.
2.3.1 Fire Brigade Panel
The Fire Brigade Panel is intended to give information related to fire
alarms in the relevant
Operation Zone
and allow the fire brigade to
operate fire alarms. The panel is identical to the
upper section
of the
operator panel.
The panel is used to silence and resound sounders, and to reset fire
alarms within a defined operation zone.
Each panel is assigned to one operation zone. Relative to its own
zone, a panel is local while it is remote to all other operation zones.
All events and actions occurring in a particular operation zone must be
handled from a local panel.
The whole system can be reset from this panel, provided that the
panel's relation to the operation zone is defined this way.
The panel displays information on fire alarms occurring in all operation
zones. However, the level of details of the given information depends
on which operation zone the information is related to.