Enabling
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 85
12.7 Enabling Fire Alarm Routing Equipment
When you enable
Fire Alarm Routing Equipment
(FARE), the output
which controls such equipment will be enabled. In the event of an
alarm, fire alarm signals may be sent to the fire brigade (configurable).
12.8 Enabling Outputs
When you enable outputs which control
Fire Protection Equipment
(FPE), in the event of an alarm, signals will be sent to trigger the
equipment. You can enable a single output, or all outputs in the
Operation Zone.
12.9 Enabling Fault Warning Routing Equipment
When you enable
Fault Warning Routing Equipment
(FWRE), the
output which controls such equipment will be enabled. In the event of
a fault, fault warning signals will be sent to, for example, the security
firm.
12.10 Enabling Carriers
A Carrier is a loop unit hosting one or several subunits.
When you enable a
Carrier
manually or when a disablement time has
been set and expires
,
the Carrier itself and all its subunits (functions)
will be enabled - with the exception of subunits (functions) that have
been disabled from other disablement sources, for example, by means
of a disable input device. The subunits that have been disabled from
other sources must also be enabled by means of the same sources.
12.11 Enabling Immediate Output Actioning
When enabling
Immediate Output Actioning
, there will be no delay on
the actioning of outputs to Fire Alarm Devices (FAD) and/or Fire Alarm
Routing Equipment (FARE) in zones configured as
Delayed Action
Detection Zones
,
Delayed Coincidence Detection Zones
or
SOLAS
Detection Zones.
It is possible to enable immediate output actioning for
all Day / Night
areas
or for
selected Day / Night areas.