Panel Overview
Operator's Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-OPERATE/FGB Rev.G, 2016-02-19,
Autronica Fire and Security AS
Page 17
Fault
The yellow Fault Warning indicator shows the
presence of a fault within the operation zone of
the operator panel.
Blinking light
Unaccepted fault warnings exist.
Steady light
All fault warnings are accepted.
Function Disabled
Steady yellow light when one or more of the
following components within the operation zone
of the operator panel are in the disabled state:
function delayed
individual points
detection zones
alarm zones
Fire Alarm Devices, Fire Alarm Routing
Equipment, Fire Protection Equipment and
Fault Warning Routing Equipment.
System Fault
Steady yellow light when a
system
fault within the
operating zone of the operator panel is present.
Testing
Steady yellow light when one or more detection
zones within the operation zone of the operator
panel have been manually set to the test state.
2.7 Indication Devices
2.7.1 Upper Section
Power
Steady green light when power is ON.
FIRE
(/ ALARM)
The red fire indicator shows that one or more
detection zones within the operating zone of the
Operator Panel are in the fire alarm state.
Blinking red light:
In the event of a fire alarm. The Fire Alarm
Devices (FAD) are still in active state.
Steady red light:
All FADs activated by the fire alarm condition
have been deactivated by operating the Silence
Alarms button. The control and indicating
equipment still remain in the fire alarm condition.
More Events
In the event of more than one alarm.
The red More Events indicator shows that several
detection zones within an operating zone are in the fire
alarm state.
Blinking red light:
In the event of a fire alarm. The Fire Alarm
Devices (FAD) are still in active state.
Steady red light:
The Silence Alarms button has been pressed. All
FADs activated by the fire alarm are no longer
active. The control and indicating equipment still
remain in the fire alarm condition.
Note that there are four market variants of this
panel (BS-420/BS-420M/BS-420G/BS-420G2). The
Indication Devices shown in this handbook deals
with the Indication devices for the standard panel
BS-420.
Fire Brig. Signalled
(/ Ext. Output Activated)
Steady red light when the message is sent to the
Fire Brigade.
Note that the name of the Fire Brigade Loop Panel’s
indicators deviate from the Fire Brigade Panel:
“Fire Brigade Signalled” is “Alarm Routing Activated“
“Test” is “Testing”