background image

      

   

                                                              

Remote Fire Annunciator

LCD-80F

PN:51338:B     ECN 06-297

          

Document 51338
08/24/05       Rev:

Summary of Contents for LCD-80F

Page 1: ...Remote Fire Annunciator LCD 80F PN 51338 B ECN 06 297 Document 51338 08 24 05 Rev B...

Page 2: ...and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a...

Page 3: ...hnical Services Department if any problems are anticipated or encountered Disconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove al...

Page 4: ...ith the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 9th Edition Operation of this product with products not tested for UL 864 9th Edition has not been...

Page 5: ...ch 16 2 2 2 Acknowledge Step 16 2 2 3 Silence 17 2 2 4 Drill Hold 2 Sec 17 2 2 5 Reset 17 2 3 LED Indicators 18 2 3 1 AC Power 18 2 3 2 Alarm 18 2 3 3 Supervisory 18 2 3 4 Trouble 18 2 3 5 Alarm Silen...

Page 6: ...Alarm Trouble Supervisory and Alarm Silenced conditions The LCD 80F is capable of performing system acknowledge silence drill and reset remotely Communication between the FACP and the LCD 80F is accom...

Page 7: ...he control panel Time date and device address from the control panel EIA 485 connects to control panel terminal port Plug in terminal blocks for ease of installation and service DIP switches control p...

Page 8: ...e DIP Switch Settings Example on page 13 The LCD 80F sounder if enabled will be activated when any new alarm or trouble is received from the panel It is silenced by an Acknowledge switch Piezo must no...

Page 9: ...e Refer to illustrations on the following page for LCD 80F connections to the MS 9200UD and MS 9600 MS 9200UD TB8 MS 9600 TB7 LCD 80F P1 Connector Terminal 2 IN Terminal 5 IN Terminal 1 OUT Terminal 4...

Page 10: ...08 24 05 P N 51338 B LCD 80F MS 9200UD Figure 1 3 FACP EIA 485 Wiring to LCD 80F EIA 485 Out to Next Device EIA 485 Out to Next Device or back to FACP EIA 485 EIA 485 Out to Next Device EIA 485 Out t...

Page 11: ...Supervision Receive Transmit OFF Supervision Receive Only One Annunciator if a single LCD 80F is the only annunciator connected to the EIA 485 loop Switch 3 must be set to the ON position to allow th...

Page 12: ...appropriate switch settings Programming Note Depending on the FACP which is connected to the LCD 80F it may be necessary to enable communication with the annunciator in the FACP programming Refer to...

Page 13: ...r function 2 DIP switch 2 OFF piezo sounder disabled requires approval of LAHJ 3 DIP switch 3 OFF Receive Only This setting is used for all annunciators except the last or only LCD 80F Annunciator on...

Page 14: ...he last LCD 80F back to the FACP 2 Up to 32 LCD 80F Annunciators may be used on the EIA 485 circuit Refer to the specific FACP manual to determine the maximum current available for powering the LCD 80...

Page 15: ...a period of over 30 seconds it will activate its local sounder if so programmed and display the following message A Communication Fault may be due to one of the following conditions FACP has not been...

Page 16: ...abled position fully counterclockwise with the key removed and access to the key restricted to authorized personnel only Do not leave the key unattended in the LCD 80F 2 2 2 Acknowledge Step When the...

Page 17: ...or at least two seconds time required to prevent accidental activations the LCD 80F will transmit a drill command to the control panel This command causes the FACP to turn on all NAC outputs and all s...

Page 18: ...or more supervi sory conditions occur such as a sprinkler valve tamper condition It turns off when the Reset switch is pressed 2 3 4 Trouble This is a yellow LED that turns on steady when one or more...

Page 19: ...depending on the type of installation desired Be certain that power is not applied to the wiring during the installation procedure Note To ensure static protection all enclosures including the LCD 80F...

Page 20: ...UNCIATOR Alm Silenced Supervisory Trouble Alarm AC Power Figure 3 2 Hardware and Backboxes LCD 80F flange LCD 80F Trim Ring replacement P N 23165 3 Gang Electrical Box P N 10103 semi flush mount 3 Gan...

Page 21: ...place the trim ring and secure with the two screws which were previously loosened Adjust the plastic trim ring to the surface of the wall before tightening the screws Do not overtighten Ack Step Silen...

Page 22: ...ur screws provided for this purpose Replace the trim ring and secure with the two screws which were previously loosened Adjust the plastic trim ring to the surface of the wall before tightening the sc...

Page 23: ...on page 13 Carefully insert the LCD 80F into the three gang electrical box and attach it using the four mounting holes on the LCD 80F flange and the four screws provided for this purpose Replace the...

Page 24: ...ator Maximum LCD 80F current draw from the power supply under normal and alarm conditions is 64 3 mA Maximum current draw from the control panel s secondary power source batteries under loss of AC pow...

Page 25: ...er strongly recommended that the power and communication wires be separate whenever possible 5 Ferrite Core P N FBD 1 is required to meet FCC Part 15 require ments if the EIA 485 wiring is not in cond...

Page 26: ...as 120 VAC service noisy elec trical circuits that are powering mechanical bells or horns audio circuits above 25 VRMS motor control circuits or SCR power circuits Note To ensure static ESD electrosta...

Page 27: ...annunciator must be left floating The shield entering the second annunciator must be connected to the three gang box or Earth Ground terminal P2 7 on the second annunciator If additional annunciators...

Page 28: ...nciator must be left floating and the shield entering the following unit must be connected to the Earth Ground terminal P2 7 on the annunciator Caution Do not allow the floating shield end no connecti...

Page 29: ...r maximum 14 application see also typical configuration 14 B backboxes 7 19 backlit 6 7 C communication 6 11 communication failure 15 Communication Fault 15 components 8 configuration see also FACP se...

Page 30: ...FACP selection 12 Fault 15 FCC Part 15 requirements 25 ferrite core 25 flange 21 23 function switches 7 11 see also switch functions 16 G grounding 19 26 28 K key switch 11 16 L LAHJ 8 11 LCD display...

Page 31: ...communication 11 reset switch 6 7 16 17 resound piezo 7 S SBB 3 backbox 19 21 semi flush mounting 21 shield no conduit 27 see also EIA 485 26 silence switch 6 16 17 specifications 9 static protection...

Page 32: ...P N 51338 B three ganged electrical boxes 22 trim ring 19 20 21 22 23 trouble LED 6 7 18 typical configuration 14 W wiring 8 9 conduit 28 distance 25 EIA 485 25 ferrite core 25 no conduit 27 power 24...

Page 33: ...33 Document 51338 Rev B 08 24 05 P N 51338 B Notes...

Page 34: ...Notes 34 Document 51338 Rev B 08 24 05 P N 51338 B...

Page 35: ...ial Authorization form from our Return Authorization Department This writing constitutes the only warranty made by the manufacturer with respect to its products The manufacturer does not represent tha...

Page 36: ...rters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com 2005 by Honeywell International Inc All rights reserved Unauthorized use of this document is strict...

Reviews: