Mounting
Annunciator Preparation
19
Document 51338 Rev. B 08/24/05 P/N 51338:B
Section 3:
Mounting
3.1
Annunciator Preparation
The LCD-80F Annunciator can be surface mounted in a three-gang
electrical box such as the P/N SBB-3 (2.75" depth) or semi-flush
mounted in a three-gang electrical box, P/N 10103 or equivalent, with a
minimum depth of 2 3/16". The LCD-80F Annunciator can also be
mounted in three gangable electrical switch boxes connected together.
Select and remove the appropriate knockout(s), pull the necessary wires
through the knockouts and mount the box in or on the wall depending on
the type of installation desired.
Be certain that power is not applied to
the wiring during the installation procedure.
Note: To ensure static protection, all enclosures, including the LCD-80F
electrical box, must be connected to earth ground! Never use the shield
for grounding purposes.
To mount the LCD-80F Annunciator in an electrical box, the trim ring
must first be removed. The trim ring is held in place by two screws
inserted through the top and bottom edge as illustrated in Figure 3-1.
Removal of the trim ring will expose a metal flange with mounting
holes. Refer to “Hardware and Backboxes” on page 20.