Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd.
69
Group
Parameter
Range
Factory Default
Unit
Alarm Setting Group
Alarm Type
See above
table.
AL-A
-
You can set alarm output (Alarm 1 Type to Alarm 4 Type)
individually.
If alarm output mode has been selected as LBA, SBA or HBA,
AL-C, AL-D modes are not available.
6.4.4
Alarm SV setting
You can set alarm output activation values. According to the selected alarm output mode,
configuration parameters (AL
□
.H/AL
□
.L) will be activated for each setting.
Group
Parameter
Range
Factory
Default
Unit
Alarm
Setting
Group
Alarm High_CH
Alarm Low_CH
Deviation alarm:
By input type –F.S. to F.S.
Absolute value alarm:
Within display range by input type
1550
℃,℉
Changing the alarm output mode or options resets the settings to the
highest or lowest values that will not trigger output in the new mode.
6.4.5
Alarm Output Hysteresis Settings
“H” shown in the image from 6-4-2. Alarm Output Mode reresents the alarm output
hysteresis. It is used to set an interval between alarm output ON/OFF periods.
Can be set individually by alarm output (Alarm 1 Type to Alarm 2 Type).
Group
Parameter
Range
Factory
Default
Unit
Alarm Setting
Group
Alarm Hysteresis_Ch
1 to 100
(Temperature H),
0.1 to 100.0
(Temperature L)
1
℃,℉
Alarm output hysteresis applies to heater burnout alarm (HBA)
in the same manner.
This parameter does not appear if Loop Break Alarm (LBA) or
Sensor Break Alarm (SBA) is selected.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......