below than LBA detection band (
LBA.B
)
during LBA monitoring time (
LBA.T
)
, alarm
output turns ON.
Common Causes of LBA Output On
Sensor error (disconnection, short)
External controller error (magnet, auxiliary relay, etc.)
External load error (heater, cooler, etc.)
Misconnections and disconnections of external network
Set alarm output mode(
AL-
□
) as loop break alarm (
LBA
) and
you can use loop break alarm.
LBA operates only when control output MV is low limit (
L-MV
),
0%, high limit (
H-MV
), or 100%.
In case of AT (auto-tuning)/manual control/stop control, loop
break alarm (
LBA
) does not operates
When alarm reset is input, it initializes LBA monitoring start time.
6.4.8.1
LBA Monitoring Time Settings
You can set the loop break monitoring time to check changes in the control subject's
temperature. Automatically setting with auto-tunning.
Group
Parameter
Range
Factory
Default
Unit
Alarm Setting Group
LBA Time_Ch1,
LBA Time_Ch2
0~9999
0
Sec.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......