6
Parameter Settings and Functions
82
© Copyright Reserved Autonics Co., Ltd.
6.5.3
Communications Parity Bit Settings
Parity bit is a data communication method that adds an additional bit to each character in
transmitted data as an indicator used to verify data loss and corruption. This parameter is
used to enable or disable the parity bit option.
SV (Setting Value)
Description
NONE
Disables parity bit.
EVEN
Sets the total bits with signal value of 1 as even numbers.
ODD
Sets the total bits with signal value of 1 as odd numbers.
Group
Parameter
Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Parity Bit
NONE, EVEN, ODD
NONE
-
6.5.4
Communication Stop Bit Settings
You can set the number of bits to mark the end of a transmitted data string.
Setting Value
Description
1
Sets end of data string to 1 bit.
2
Sets end of data string to 2 bit.
Group
Parameter
Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Stop Bit
1, 2
2
-
6.5.5
Response Wait Time Settings
Set a standby time to mitigate communication errors when communicating with a slow
master device (PC, PLC, etc.). Once a standby time is set, the controller will respond after
the defined standby time has elapsed.
Group
Parameter
Range
Factory
Default
Unit
Option Setting Group
(Communication Setting)
Response Wait
Time
5 ~ 99
20
ms
Shorter standby times can cause communication errors in the master
device.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......