6
Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd.
87
6.6.3.3
SV for Multi SVs
Designate the value of each SV for Multi SVs.
Group
Preceding
Condition
Parameter
Range
Factory
Default
Unit
Control Setting
Group
-
Multi SV
1EA, 2EA, 4EA
1EA
-
Operating Group
(Control
Operation)
Multi SV
Multi SV No.
SV-0 to SV-3
SV-0
Operating Group
(Control
Operation)
Multi SV
SV-0 to SV-3
SV Low-limit to
SV High-limit
0
℃,℉
6.6.4
Digital Input
6.6.4.1
Digital Input Terminal Settings
When send the signal to the external digital input (DI-1, DI-2) terminal, the settings of the
digital input
□
_Func parameter will perform. When powers on, it will activate after
checking the digital input terminal.
Setting Value
Description
OFF
No function.
STOP
If DI-1,DI-2 terminals are shorted, the stop feature will perform, but to
change run/stop through communication will not perform.
AL-RESET
If DI-1,DI-2 terminals are shorted, the forced deactivation of alarm
output will perform, but to deactivate the alarm output through
communication will not perform.
Manual
If DI-1,DI-2 terminals are shorted, the manual control feature will
perform, but to change auto/manual control through communication
will not perform.
Multi-SV
By combinational logic of the digital input(DI-1,DI-2), it is possible to
select multi SV NO. (SV-0~ SV-3), but it is not possible to select multi
SV NO. through communication.
In the case one of DI-1 or DI-2 being set for Multi SV, SV-0 is selected as the SV if
the terminal's external contact signal is off and SV-1 is selected if the signal is on.
If both DI-1 and DI-2 are configured for Multi SV, you can select the SV using
combinational logic of the terminals. If changes multi SV from 4EA to 2EA, the DI-2
will be automatically turned off. If changes multi SV from 4EA to 1EA, both DI-1 and
DI-2 will be turned off.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......