6
Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd.
63
6.3.3.1
Proportional Band Settings
When PV (Present Value) is within the proportional band (P), the ON/OFF ratio needs to
be adjusted during the proportional period (T). The defined proportional control (time
proportional control) section is referred to as the proportional band.
Group
Preceding
Condition
Parameter
Range
Factory
Default
Unit
Control
Operation
Group
Heating, PID
Heating_Proportional Band
0.1 ~ 999.9
10.0
℃
Cooling, PID
Cooling_Proportional Band
6.3.3.2
Integral Time Settings
MVs from integral and proportional operation become the same when deviation is
consistent. The time taken for the two MVs to match is called the integral time.
Group
Preceding
Condition
Parameter
Range
Factory
Default
Unit
Control
Operation Group
Heating, PID
Heating_Integral Time
0 ~ 9999
0
Sec.
Cooling, PID
Cooling_Integral Time
Integral control is not conducted if the integral time is set to 0.
Setting the integral time too short can intensify Correction
Movements and cause hunting.
6.3.3.3
Derivative Time Settings
In accordance with the deviation of the ramp, the time taken for the MV gained from
derivative operation to reach the MV gained from proportional control is called the
derivative time.
Group
Preceding
Condition
Parameter
Range
Factory
Default
Unit
Control
Operation
Group
Heating, PID
Heating_ Derivation Time
0 ~ 9999
0
Sec.
Cooling, PID
Cooling_ Derivation Time
Derivative control is not conducted if the derivative time is set to 0.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......