6.4.6
Alarm Output Method Settings
Relay type can be set at alarm output.
N.O. (Normally Open) stays open when normal and closes in the event of an alarm.
N.C. (Normally Closed) stays closed when normal and opens in the event of an alarm.
Front LED Indicators
Change
Alarm Occurs
Alarm Output
Front LED
N.O.
OFF
Open
□ OFF
ON
Close
■ ON
N.C.
OFF
Close
□ OFF
ON
Open
■ ON
Group
Parameter
Range
Factory
Default
Unit
Alarm Setting Group
Alarm NO/NC
NO, NC
NO
-