6.1.6
SV High/Low-limit Settings
You can limit the SV (Setting Value) range within the temperature range of the sensor or
analog input type in order to prevent the system from controlling with improper SV.
Group
Parameter
Range
Factory
Default
Unit
Initial Setting Group
SV High-limit
See below.
1350
℃/℉
SV Low-limit
-200
SV Low-limit : Low-limit sensor value to SV high-limit - 1 digit
SV High-limit : SV low-limit + 1 digit to high-limit sensor value
Attempts to set the limits outside the min/max input range, or
analog's high/low-limits, are not accepted. Instead, the previous
settings are retained.
SV (Setting Value) can only be set within the SV low-limit and
SV high-limit.
SV low-limit cannot exceed SV high-limit.
Changing the input sensors automatically changes the SV
high/low-limit settings to max/min values of the changed
specification (temperature sensor input), or to high/low-limit
scale values (analog input). The user is required to reset related
settings.
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......