6
Parameter Settings and Functions
80
© Copyright Reserved Autonics Co., Ltd.
6.5
Communications
This feature is used for external higher systems (PC, GP, etc.) to set the controller's
parameters and to monitor the controller. It can also be used to external devices.
No redundant unit addresses may exist along the same communication line. The
communication cable must be a twist pair that supports RS485.
Interface
Category
Description
Standards
EIA RS 485-compliant
Max. Connections
31 (Address: 01 ~ 31)
Communication
Two-wire, half duplex
Synchronization
Asynchronous
Valid Communication
Distance
Max. 800 m
BPS (Bits Per Second)
2400, 4800, 9600, 19200, 38400 bps
Response Standby
5 ms to 99 ms
Communication Start Bit
1 bit (fixed)
Data Bit
8 bit (fixed)
Communication Parity Bit
None, Even, Odd
Communication Stop Bit
1, 2 bit
Protocol
Modbus RTU (character = 11 bit. fixed)
6.5.1
Communication Exchange Number Settings
You can assign a unique address to each device.
Users can set communication address using both SW1 (communication address
setting switch) and SW2 (communication group change switch).
Setting range: 01 ~ 31
Factory default 01
Summary of Contents for TM Series
Page 1: ...User Manual ...
Page 2: ......
Page 10: ...Handling Precautions x Copyright Reserved Autonics Co Ltd ...
Page 14: ...Table of Contents xiv Copyright Reserved Autonics Co Ltd ...
Page 23: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 23 1 4 2 Other Parts ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 40: ...4 Connections and block diagram 40 Copyright Reserved Autonics Co Ltd ...
Page 44: ...5 Preparation and Startup 44 Copyright Reserved Autonics Co Ltd 5 3 2 Multiple Modules ...
Page 57: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 57 Example Ramp Graph ...
Page 90: ...6 Parameter Settings and Functions 90 Copyright Reserved Autonics Co Ltd ...
Page 96: ......
Page 97: ......